Researchers link synchronized power grid frequency drops to batteries

Follow on Telegram
Coordinated disturbances haunt grids worldwide. Here’s how researchers solved the mystery. | TechCrunch
Image Credits:Daniel Balakov (opens in a new window) / Getty Images · Image source ↗

A research group from Germany’s Forschungszentrum Jülich found that regular drops in power grid frequency may be linked to stationary batteries checking their charge at the same time. TechCrunch reports on the team’s work and findings.

According to the publication, power grid operators had recorded small frequency dips roughly once a minute for years. What was unusual was that they occurred simultaneously in grids across different countries and continents. German operator Tennet Germany brought the mystery to Dirk Witthaut, a researcher at Forschungszentrum Jülich. The team spent several years investigating and modeling it.

Reported by techcrunch.com.

Grid stability depends on keeping frequency within the proper limits. Significant fluctuations can cause outages, while uncontrolled dips can damage power plant equipment, especially hydro turbines. The team first looked at hydropower, since turbine vibrations can cause low-frequency oscillations. However, a model of a hydroelectric plant did not explain why the signal occurred continuously every minute.

The researchers then hypothesized that such a precise rhythm might be linked to devices that operate according to a clock. At the Jülich campus, they installed over 80 power quality meters. The instruments recorded frequency, voltage, current and power every three seconds. The measurements showed a peak every minute at a transformer connected to a battery energy storage system.

According to the team’s findings, many stationary batteries—from uninterruptible power supplies in data centers to large grid-connected batteries—check their charge level every minute. Because these devices are connected to the internet, their clocks run almost in sync. An individual check creates a nearly imperceptible disturbance, but when many devices do it at the same time, the effect becomes visible across the grid.

To test their explanation against power grid data, the team contacted operators and analyzed Ireland. According to data cited by TechCrunch, data centers accounted for 18% of the load on Ireland’s grid in 2022, and each had a fleet of uninterruptible power supplies. Between 2016 and 2021, the frequency dip that occurred every minute there increased from 3 to 12 millihertz. More recently, some dips exceeded 20 millihertz.

Ireland’s power grid operates at a frequency of 50 Hz and is designed to handle fluctuations of up to 200 millihertz in either direction, but the operator aims to keep them within 100 millihertz. The recorded dips of up to 20 millihertz are not large on their own, but the researchers warn that other loads could add their own frequency drops and intensify the overall effect.

The proposed solution is not to check the charge exactly at the start of every minute. The researchers advise manufacturers of uninterruptible power supplies and grid batteries to randomize the timing of such checks so that devices do not act simultaneously.

The team also found periodic fluctuations in power consumption in some Internet of Things devices, including a smart oven and Raspberry Pi clusters. According to TechCrunch, the researchers believe a software fix could address this factor too, but some devices remain without updates. The publication notes that regulators could address the problem in their jurisdictions, but coordinated changes across the global grid require international coordination.